Ruggedization against high shock, vibration, and
humidity
• MS connectors
• 400 Hz input and / or output
• Chassis Slide
guides
• Solid state transfer switch (Standard
on some models) Additional battery back-up time
(up to 24 hours available)
• Premium batteries with up to 10 year life
• Input and output connectors
• Additional Meters
• RS-232
Interface Port
• Custom Paint
• Custom Enclosures
• RUPS 2000
UPS monitoring and controlling software.
|
|

Input
| Voltage
(select): |
120, 208,
220, 240 VAC, 1Ø 120/208, 220/380
3Ø |
Automatic: 120, 220, 240 VAC
Frequency: 50 Hz, 60 Hz, and 400 Hz available
Automatic: 45-65 Hz
Connections: Line cord, terminal block or
MS connector
Output
Voltage (specify): 120, 208, 220, 240 VAC, 1f
- 3f output available
Frequency: 50 Hz, 60 Hz, and 400 Hz available
Voltage regulation: +/-1% no load to full
load
Dynamic voltage regulation: +/-10% for 100%
load change
Frequency regulation: +/-0.5% no load to
full load (Free running)
Connections: Line cord, terminal block or
MS connector
Power factor: 0.7 lead to 0.7 lag
Harmonic distortion: 5% THD
Efficiency at full load: 75% to 80% AC-AC
Typical
Sync & phase lock range*: +/-3 Hz Typical
Dimensions
5-6 KVA Model Dimensions: 8.75"
High x 19" Wide x 23.25" Deep
External Battery Drawer Dimensions:
7" High x 19" Wide x 20.75" Deep
5 KVA UPS Drawer Weight: 200 Pounds
(typical)
6 KVA UPS Drawer Weight: 225 Pounds
(typical)
External Battery Drawer Weight:
200 Pounds (typical)
| Overload: |
125% for 10 minutes 1000%
for one cycle (Via optional static
transfer switch) |
MTBF: 30,000 hours per MIL-HDBC-217
MTTR: 30 minutes per qualified personnel
* SYNC disabled on certain models
Environmental
Ambient operating temperature range:
-20° to +50° C*
Storage temperature range: -40° to +60°
C*
Humidity: to 95% RH non-condensing – Designed
to meet MIL-STD-810. All boards conformal coated
with Acrylic MIL-I-46058 Type R.
Shock: 20g, 11 mS half sinewave – Designed
to meet MIL-STD-810 optionally
EMI: Designed to meet FCC Part 15, Class
A. Designed to meet MIL-STD-461 with optional
additional filtering.
*For best results, batteries
must be kept at 25 degrees Celsius ambient temperature.
Extreme low temperatures will result in reduced
run time, while extreme high temperatures result
in significantly reduced battery lifespan. Click
here for more information on THE
EFFECTS OF EXTREME TEMPERATURES ON BATTERIES.
Elevation:
15,000
ft. (4,572 m) operating**
40,000
ft. (12,192 m), non-operating**
**For batteries, please follow battery
manufacturer instructions regarding recommended
elevation parameters.
Audible noise:
Less than 55 dBA at 5 ft. (1.5 m)
Transportation
and handling :
MIL-STD-810C
Protective Features
Circuit Breakers: Battery
Charger Input, Battery Input
Fuses: Inverter Input, AC Bypass Input
Low Battery Shut Off
Overload Protected
Thermal Protection
Output Short Circuit Protection
Transient Protection (available to MIL-STD-1399
Audible Alarm with Silence Switch
Standard Remote
Contacts
Major Alarm: Logic Fault, Low Battery, Over-Temperature,
UPS Off, UPS Overloaded
Minor Alarm: Utility Off, Load on Utility
Standard
Front Panel Diagnostics
System Status: Green/Red
Utility Off: Red
UPS Off: Red
Low Battery: Red
Logic Fault: Red
UPS Overload: Red
Over-Temperature: Red
Load on Utility: Red
AC & DC Voltage: Meter
|