100 School St. Bergenfield, NJ 07621 USA Tel: 201.385.0500  Fax: 201.385.0702  Email: novasales@theallpower.com


Switch Mode Power Supplies from 15W to 12kW.DC-DC Converters with single and multiple outputs from 50W to 2000W. Hot Swap, Redundant, Battery Backup, Power Factor Correction, Universal Input, Single and Multiple Output.

Mid Eastern Industries, Standard and specialty linear power supplies,Linear Power Supplies up to 1200 Volts.  Computer programmable, ELDAN division - Low price lab power supplies.

Prototype Metal designs, engineers, and manufactures custom products for the telecommunications and related industries. We offer complete design and engineering services from concept through production to any level of integration you require.

Power Supplies, DC-DC Converters

Linear Power Supplies

Precision Sheet  Metal

Nova Electric is ISO-9001 UL Registered Firm.

Main

What's    AT Nova? Application Notes Download (pdf) SpecS.  Ordering Info Terms & Conditions NOVA QUALITY Contact Us
 

Company PrOFILE

Information Request Form

 
 

Products

DC-AC INVERTERS

Ups power systems

Frequency Converters

Custom Designs

 

EMPLOYMENT

Iso 9001 Certification

Contact Us

 

 

ISO-9001

 

 

THE RS 232 OPTION FOR NOVA GALAXY-SERIES UPS SYSTEM

 

COMMUNICATION OPTIONS: UNLESS NOTED OTHERWISE, ALL NOVA GALAXY-SERIES UPS SYSTEMS ARE EQUIPPED WITH RELAY CLOSURES AS STANDARD EQUIPMENT. CONNECTION TO THE STANDARD RELAY CLOSURES IS VIA A 9-PIN "D" CONNECTOR, USUALLY LOCATED ON THE REAR PANEL OF THE UPS ENCLOSURE. THESE CLOSURES CAN BE MODIFIED TO WORK WITH OUR OPTIONAL RUPS 2000 UPS MONITORING SOFTWARE. THIS CONFIGURATION ALLOWS FOR UNI-DIRECTIONAL (UPS TO COMPUTER) COMMUNICATION (THE UPS WILL INFORM THE COMPUTER ONLY WHEN A CHANGE IN STATUS OCCURS). BY COMPARISON, TRUE "INTELLIGENT RS-232" CONFIGURATION (ALSO AVAILABLE OPTIONALLY) ALLOWS FOR BI-DIRECTIONAL (UPS TO COMPUTER AND COMPUTER TO UPS) COMMUNICATION (THE COMPUTER OPERATOR CAN ASK THE UPS CURRENT STATUS AT ANY TIME, EVEN IF THERE HAS BEEN NO CHANGE).

 

BE ADVISED THAT ON CERTAIN UPS MODELS, THIS "INTELLIGENT RS-232" CONFIGURATION MAY REQUIRE AN ADDITIONAL EXTERNAL DRAWER TO ENCLOSE THE ADDITIONAL COMPONENTS REQUIRED – PLEASE CONSULT THE FACTORY FOR DETAILS.

 

BASIC INSTRUCTIONS: THE RS 232 OPTION SUPPLIED WITH NOVA GALAXY MODEL UPS SYSTEMS INCORPORATES ALL OF THE PROGRAM FUNCTIONS WITHIN THE RS 232 CONTROLLER CARD SUPPLIED AS PART OF THE POWER SUPPLY.

THE USER MUST ONLY SUPPLY A COMPUTER CAPABLE OF USING ANY SERIAL COMMUNICATION PROGRAM THAT ALLOWS THE COMPUTER TO OPERATE AS A REMOTE TERMINAL. A “HYPERTERMINAL” PROGRAM WILL ALSO DISPLAY THE BINARY OR TEXT OUTPUT STATUS.

A SUGGESTED TERMINAL PROGRAM IS PROCOMM 2.42 BY DATASTORM TECHNOLOGIES, INC. (P.O. BOX 1471, COLUMBIA, MO 65205).

AN OPTIONAL COPY OF “PROCOMM” CAN BE INCLUDED ON A DISK PROVIDED WITH THE UNIT.

PLEASE ENTER “ALT I” WHILE “PROCOMM” IS RUNNING TO VIEW THE USER REGISTRATION REQUIREMENTS.

THE SUGGESTED EMULATION IS VT100.

SET-UP FOR COMMUNICATION IS -- BAUD:  9600; 8 BIT; NO PARITY; 1 STOP BIT.

X ON – X OFF PROTOCOL.  HARDWARE PROVIDES FLOW CONTROL.

 

CONNECTOR HARDWARE ON THE UNIT

 

9 PIN “AT” STYLE CONNECTOR

(COMPUTER END)

 

                                                            UPS CABLE END

 

            TXD 2>----------<3                            RXD

            RXD 3>----------<2                            TXD

            GND 5>----------<1                            GND

 

25 PIN “XT” STYLE CONNECTOR

 

            TXD 2>----------<3                            RXD

            RXD 3>----------<2                            TXD

            GND 7>----------<1                            GND

 

FIGURE 1

______________________________________________________________________

 

STATUS REPORT – NOVA GALAXY UPS

UTILITY POWER ON (OFF) 
DC/AC INVERTER STATUS OK (FAIL)  
BATTERY STATUS OK (LOW)
LOGIC STATUS   OK (FAULT)  
UPS OVERLOAD      NONE (OVERLOAD)  
UPS TEMPERATURE   OK (OVER TEMPERATURE)  
BATTLE SHORT        OFF (ON)

KEYBOARD CODES

 

STATUS UPDATE:  AUTOMATIC WHEN THERE IS A STATUS CHANGE, OF KEY “?”.  REWRITE SCREEN: KEY (ENTER).

DESCRIPTION OF OPERATION: WHEN THE UNIT IS TURNED ON AND CONNECTED TO THE PC THROUGH THE RS 232 PORT, A CONTROL SCREEN IS PRESENTED TO THE OPERATOR THAT APPEARS AS IN FIGURE 1.

REPORT ITEMS 1 THROUGH 7 ARE STATUS REPORTS TRANSMITTED FROM THE UNIT.

CHANGE OF STATUS FROM ANY INPUT WILL CAUSE AUTOMATIC UPDATE OF THE SCREEN.

MANUAL UPDATE MAY BE ACCOMPLISHED BY ENTERING “?” AT ANY TIME.

IF THE STATUS OF ANY OF THE ITEMS 1 THROUGH 6 IS GOOD, THE RESPONSE PRESENTED ON THE SCREEN IS THE NON-BRACKETED PRESENTATION IN FIGURE 1.

IF THE STATUS OF ANY OF THE ITEMS 1 THROUGH 6 IS AN ALARM CONDITION, THE BRACKETED RESPONSE IS PRESENTED ON THE SCREEN.

STATUS ITEM 7 INDICATES THE STATE OF THE BATTLE SHORT FUNCTION PROVIDED VIA THE RS 232 INPUT.

TO TURN THE BATTLE SHORT FUNCTION ON, THE USER WILL TYPE CAPITAL “B” AND A CARRIAGE RETURN TO INITIATE THE COMMAND.  COMMANDS MUST BE ENTERED IN CAPITAL LETTERS.

TO TURN THE BATTLE SHORT FUNCTION OFF, THE USER WILL TYPE CAPITAL “B” AND A CARRIAGE RETURN TO INITIATE THE COMMAND.  COMMANDS MUST BE ENTERED IN CAPITAL LETTERS.

 

FOR MORE INFORMATION, PLEASE CONSULT THE FACTORY DIRECT.