|
| |
Introducing Nova's Custom
PORTABLE MILITARIZED DC-AC Inverters

Click
here for APPLICATION NOTES
PORTABLE AC POWER WHEREVER AND
WHENEVER YOU NEED IT!
Rugged, Lightweight Design for
Harsh Environments
22-32 VDC Operating Input / 1 kVA
- 3 kVA
Product Description:
This specialized series of inverters was developed specifically for mobile
military applications, and is currently in use by NATO forces internationally. The rugged,
lightweight design and portable enclosure, coupled with Nova's proven reliability, make
this series ideal for any Harsh Environment application! These units are especially
designed for use in ground vehicles, to convert 28 VDC vehicle battery power into AC
to power test equipment or various instrumentation. The inverters can be either
mounted within vehicles or easily hand-carried by one person. In addition to the standard
equipment found on our standard Galaxy-Series inverters, the MILITARIZED
PORTABLE models also
contain other key features, including:
- Wide Temperature Operation - Can
withstand operating temps between -40 to +60 degrees Celsius
- Extensive EMI Filtering - The
inverters feature an Input EMI Filter for attenuating input noise and common mode noise to
comply with portions of MIL-STD-461. An Output EMI Filter is also included to filter the
output leads and deliver clean power to the load.
- Heavy-Duty Input Circuit Breakers -
Act as ON / OFF switch and as additional protection. (rating varies by model)
- Additional Ruggedization - The
inverters are ruggedized against shock, vibration, and humidity to meet MIL-STD-810. In
addition, all boards are conformal coated for extra protection against high-humidity and
potential fungus growth.
PARTIAL PRODUCT LISTING
60 Hz
MODELS |
OUTPUT
VAC |
OUTPUT
FREQ
(Hz) |
CONTINUOUS
OUTPUT
POWER |
APPROX.
WEIGHT
(LB) |
SIZE
(H x W x L)
(INCHES) |
GL1K60-24 WTO-EMC |
120 |
60 |
1 KVA |
20 |
6.5 x 10.5 x 21.6 |
| GL1.5K60-24 WTO-EMC |
120 |
60 |
1.5 KVA |
28 |
Consult Factory for details |
| GL2K60-24 WTO-EMC |
120 |
60 |
2 KVA |
33 |
| GL2.5K60-24 WTO-EMC |
120 |
60 |
2.5 KVA |
37 |
| GL3K60-24 WTO-EMC |
120 |
60 |
3 KVA |
41 |
50 Hz
MODELS |
OUTPUT
VAC |
OUTPUT
FREQ
(Hz) |
CONTINUOUS
OUTPUT
POWER |
APPROX.
WEIGHT
(LB) |
SIZE
(H x W x L)
(INCHES) |
GL1K50-24(220) WTO-EMC |
220 |
50 |
1 KVA |
20 |
6.5 x 10.5 x 21.6 |
| GL1.5K50-24(220) WTO-EMC |
220 |
50 |
1.5 KVA |
28 |
Consult Factory for details |
| GL2K50-24(220) WTO-EMC |
220 |
50 |
2 KVA |
33 |
| GL2.5K50-24(220) WTO-EMC |
220 |
50 |
2.5 KVA |
37 |
| GL3K50-24(220) WTO-EMC |
220 |
50 |
3 KVA |
41 |
400 Hz
MODELS |
OUTPUT
VAC |
OUTPUT
FREQ
(Hz) |
CONTINUOUS
OUTPUT
POWER |
APPROX.
WEIGHT
(LB) |
SIZE
(H x W x L)
(INCHES) |
GL1K400-24 WTO-EMC |
115 |
400 |
1 KVA |
20 |
6.5 x 10.5 x 21.6 |
| GL1.5K400-24 WTO-EMC |
115 |
400 |
1.5 KVA |
28 |
Consult Factory for details |
| GL2K400-24 WTO-EMC |
115 |
400 |
2 KVA |
33 |
| GL2.5K400-24 WTO-EMC |
115 |
400 |
2.5 KVA |
37 |
| GL3K400-24 WTO-EMC |
115 |
400 |
3 KVA |
41 |
*Three-Phase Inverters:
Nova IGL-Series and GL-Series inverters can be arranged for three-phase operation by the
customer upon request. We accomplish this by packaging three separate single-phase
inverters as one three-phase unit or as a series of modules. All popular nominal DC input
voltages and AC output voltages are available upon request, in sizes from 1.5-60+ KVA.
Please consult the factory for details.
Specifications
Electrical
Input Voltage: 22-32 VDC (Extended range available)
Output Voltage: See Table
Frequency: 50 Hz, 60 Hz, 400 Hz (+/-0.5%)
Frequency Regulation: +/-0.5% N.L. to F.L.
Voltage Regulation: +/-1.5% N.L. to F.L.
Efficiency: Approximately 80% (depending on model)
Reactive Load: 0.75 Lead to 0.75 Lag
Distortion: 5% THD, 3% Single Harmonic
Overload: 125% for 5 minutes
| Overload Protection Range: |
Automatic overload &
short circuit protection |
| Sync & Phase Lock Range: |
+/-3 Hz, Typical (50/60
Hz models) |
| Transient Response: |
Approx. 1/4 cycle recovery to
95% of nominal |
Environmental & Mechanical
| Operating Temp: |
-40°C to +60°C |
Cooling: By internal DC brushless fan
Vibration: MIL-STD-810
Shock: 20g, 11 mS half sinewave, MIL-STD-810
Humidity: To 95% RH non-condensing, MIL-STD-810
| EMI: |
Designed to meet FCC Part 15, Class A, and
portions of MIL-STD-461 |
Applications
Utilizing high frequency PWM topology, these
models offer volume and weight advantages
suitable for severe environment and high reliability
applications such as:
- Military programs, vehicular, shipboard
- AC Power from vehicle battery
- Communications
- Shelters
- HMMWV applications
- Cellular sites
Standard Features
- Pure Sinewave Output
- Small Size
- Lightweight, extremely compact
- High reliability, MTBF exceeds 100,000 hours
- OV, O.L. and O.T. protected
- MTTR below 30 minutes; modular design
- Withstands high reactive load
- Tight voltage and frequency regulation
- Output fault alarm (relay closure)
- Boards are conformal coated
Available Options
- Special output voltages and frequencies
- Provision for 3 Phase connection
with 2 more identical units
- Custom painting and marking
- High inrush for motor start
- Transfer switch to alternate AC source
- Switchable 50/60 Hz output
|
Contact Us
Visa and MasterCard Accepted

|