Nova Centralion Series True Online Freestanding UPS
Coni
(1KVA / 2 KVA )
Nova Electric proudly introduces our family of
CONI 1-2 KVA True On-Line UPS Systems. This attractive new freestanding line is designed specifically for both personal and commercial applications.
Protect your CAD workstation computers, peripherals, networks, communications equipment, and other sensitive apparatus.
True double sine wave
conversion.
Microprocessor control.
Power factor correction.
IGBT Inverter.
RS-232 communication
interface.
Peak current limit protection.
Optional bundle software
automatically save your valuable files
before auto shutdown.
19'' rack mount available.
Extendable back-up time w/charger
.
|
 |
|
CONI TRUE ON-LINE UPS SPECIFICATION
| MODEL |
|
CONI-1K
|
CONI-2K
|
| CAPACITY |
|
1000VA
|
2000VA
|
| INPUT |
VOLTAGE |
100VAC,
110VAC, 220VAC, 230VAC or 240VAC |
| VOLTAGE
RANGE |
160-270VAC
or 85-135VAC |
| FREQUENCY |
50Hz
or 60Hz +/-5% |
| POWER
FACTOR (FULL LOAD) |
>0.95 |
| PHASE |
SINGLE |
| OUTPUT |
VOLTAGE |
100VAC,
110VAC, 220VAC, 230VAC or 240VAC |
| VOLTAGE
REGULATION |
+/-3% |
| FREQUENCY |
50Hz
or 60Hz |
| FREQUENCY
REGULATION |
+/-0.5% |
| HARMONIC
DISTORTION |
<4%
AT 100% LINEAR LOAD |
| OUTPUT
WAVEFORM |
PURE SINE
WAVE |
| EFFICIENCY |
AC
TO AC |
>80% |
| BATTERY |
BATTERY
TYPE |
SEALED
LEAD ACID BATTERY, MAINTENANCE FREE |
| BATTERY
SIZE |
12V/7AH |
| NUMBER
OF BATTERIES |
4
|
6
|
| BACK
UP TIME |
5-20
MINUTES |
| RECHARGE
TIME |
8-10
HOURS TO 90% AFTER COMPLETE DISCHARGE |
| TRANSFER
TIME |
AC
FAULT |
ZERO |
| UPS
TO BYPASS OR VICE VERSA |
LESS
THAN 4MS |
| INDICATOR |
LINE |
GREEN
LED |
| INVERTER |
GREEN
LED |
| BY-PASS |
YELLOW
LED |
| FAULT |
RED
LED |
| CAPACITY |
GREEN
LED BAR |
| AUDIBLE
ALARM |
BATTERY
DISCHARGE |
SOUNDING
EVERY 4 SECONDS |
| DISCHARGE
OVER 30 MINUTES |
SOUNDING
EVERY 15 SECONDS |
| BATTERY
LOW |
SOUNDING
EVERY SECOND |
| OVERLOAD |
RUSH
BEEPING |
| FAULT |
CONTINUOUSLY
BEEPING |
| PROTECTION |
OVERLOAD |
110-140%
DELAY 20 SECONDS, >140% DELAY 10 CYCLES |
| SHORT
CIRCUIT |
INVERTER
AUTO CUT-OFF THEN TRANSFER TO FAULT |
| OVER
TEMPERATURE |
INVERTER
AUTO CUT-OFF WHEN HEAT SINK TEMP. OVER 90° C, |
| |
THEN
TRANSFER TO BY PASS |
| DIMENSION |
DxWxH inches |
18.3 X
7.48 X 10
|
20.9
X 7.48 X 10
|
| WEIGHT |
NET
WEIGHT (BATT. INCLUDE) |
46.2lbs
|
66lbs
|
| SHIPPING
WEIGHT (BATT. INCLUDE) |
50lbs
|
70.4lbs
|
| ENVIRONMENT |
OPERATING
TEMPERATURE |
0-40°C;
32-104°F |
| RELATIVE
HUMIDITY |
<95%
(NON-CONDENSING) |
| NOISE
LEVEL |
<45dB
(AT 1 METER) |
| INTERFACE |
|
SMART
RS-232 COMMUNICATION INTERFACE |
|
|
|
|