5 KVA NAVY GALAXY SERIES
TRUE ON-LINE UPS
|
This rugged Navy Galaxy-Series UPS System
is specifically designed for submarine and
shipboard applications in compliance to MIL-STD-1399,
MIL-STD-461, MIL-STD-901,MIL-STD-810, AND
MIL-STD-740. The example pictured is a compact
5 KVA unit built for use on the US Virginia
Class Submarine, as well as other high profile
shipboard and submarine applications in US
and US-friendly fleets worldwide. This model
has a three-phase power factor corrected (PFC)
input of 115 VAC L-L, 50/60 Hz per MIL-STD-1399
Section 300 Type I and a pure sinewave galvanically
isolated output of 115 VAC, Single-Phase.
Single-phase input is optional, and output
frequency is available in 50, 60, or 400 Hz
(specify.) This UPS System contains all of
the features standard on other Galaxy-Series
units, as well as additional features that
make it ideal for Naval applications.
|

|
|
RUGGED
TRUE ON-LINE UPS
NAVY GALAXY SERIES
Model Selection
NGRS11-5K60-115(D)-115 |
5 |
115VAC L-L |
115VAC |
125 |
10 min |
120 |

• RS232 or SNMP Interface
• RUPS 2000 Computer Interface
• Chassis Slides
• MS Connectors Mates
• High Speed Mechanical Transfer Switch
• Custom Paint & Markings
|
|

ELECTRICAL
Optional Input Voltages available (select):
115/200, 120/208, 220/380 3Ø
Optional Input Frequencies available (specify): 50, 60 or 400 Hz
Optional Output Voltages Available (specify): 115, 120, 208, 220, 230, 240 VAC 1Ø
Output Frequency (specify): 50, 60 or 400Hz
Voltage Regulation: +/-
2% NL to FL
Frequency Regulation: 0.1%
Harmonic Distortion: 2%
THD Typical
5% Max
Input Power Factor: 0.99
Efficency at full load: 82% typical
Overload: 125%
for 5 minutes
EXTERNAL BATTERIES
3.5" High x 19" Wide x 24.125" Deep
(120 lb) rack- mount battery drawer containing sealed maintenance-free,
user-replaceable permium wide-temp batteries rated for 8-10 years lifetime
(96 VDC nominal). Battery cabinets and racks available for UPS runtime
from 5 minutes to 24+ hours.
PROTECTIVE FEATURES
AC & DC Input Circuit
Breakes, Low Battery Shut
Off, Overload and Thermal
Protection, Audible Alarm
with Silence Switch, and
Optional EPO.
ENVIRONMENTAL
Operating Temperature: -20° to
+50° C per MIL-STD-810D
Storage Temperature
Range: -30° to
+60° C
Humidity: to
95% non-condensing
Elevation: 15,000
Ft. (4.572m) operating
40,000 Ft (12.192m) non-operating
Audible noise: Less than 55 dBA at 5 ft. (1.5 m)
EMI: Per
MIL-STD-461B/E
Vibration: Per IEC
68-2-6 Type I
Shock: 20g
for 20ms half sinewave
per MIL-STD-901C Grade
A
Structureborne
Noise: MIL-STD-740B
Grade A
MTBF: 30,000 hours
MTTR: 30 Minutes
ALARMS
AND DIAGNOSTICS
System Status: Green/Red
Utility Off: Red
UPS Off: Red
Low Battery: Red
Logic Fault: Red
UPS Overload: Red
Over-Temperature: Red
Load on Utility: Red (with XFR SW option)
COMUNICATIONS
Alarm Contacts: Standard
RS 232 or SNMP: Optional
|
SYSTEM COMPLIANCE
Additional Ruggedization to meet MIL-STD-901,
IEC 68-2-6, and MIL-STD-810: The
UPS System’s construction is extremely
robust, and ruggedized throughout. All
components and modules within the unit
are mounted using additional steel brackets
and heavy-duty stainless-steel hardware,
which is then further secured using Loctite
and RTV where required. All boards are
conformal-coated (Acrylic MIL-I-46058
Type R) for maximum resistance to potential
condensation and fungus growth. The unit
was tested and qualified as follows:
MIL-STD-901C for Grade A, Class
II Equipment: Shock test with half sinewave,
20ms duration, 15g peak acceleration shock
pulse.
IEC 68-2-6 for Type I Testing:
Between 3-10 Hz amplitude to be 0.5mm. Between
10-50Hz acceleration to be 2 m/s2
MIL-STD-810D: Operating Temperature
Tests including High Temperature Test per
Procedure II, Method 501.2, Table 501.2-II
Ambient Air, 4 Cycles @ 24 Hours per cycle,
Low Temperature Test per Procedure II, Method
505.2, Table 505.2-I Region CO, 4 Cycles
@ 24 Hours per cycle, and Temperature Shock
Test per Procedure I, Method 503.2, between
0-40 degrees Celsius, 4 Cycles @ 24 Hours
per cycle.
Internal EMI Reduction Package to meet MIL-STD-461:
The design of this unit is specifically
focused on reducing EMI emissions. The
UPS contains substantial internal filtering
to minimize EMI emissions. Inputs which
may be susceptible to transients are
protected by several methods, including
MOVs. All internal magnetics are shielded
with copper and mu-metal to further minimize
emissions. The compact rack mount chassis
is specifically treated with low surface
resistivity finishes on the interior.
All aluminum parts are treated with clear
irridite. The steel parts are treated
with zinc plate, followed by a clear
chromate. All exterior portions (except
for mating surfaces) are then painted
with glossy ANSI-61 gray to assure excellent
bonding of mating sheet metal parts.
All input and output ventilation filters
include metal honeycomb-style filters.
The unit was tested and qualified as
follows:
MIL-STD-461B Part VI for EMI Class A5: CE01,
CE03, CS01, CS02, CS06, CS09, RE01, RE02,
RS01, RS02, RS03.
Super-Rugged, Long Life Hawker
Energy Batteries: External Hawker
Energy sealed, maintenance free batteries
provide 10 minutes back up time at full
load. These batteries are extremely resistant
to shock, vibration, and wide temperature
ranges. Also, they have a very long service
life (8-10 years measured at 25 degrees
Celsius ambient temperature) for a minimum
of maintenance. The batteries are user replaceable.
Structureborne and Airborne Noise:
The rugged Navy Galaxy-Series UPS System
was tested and qualified to MIL-STD-740B
for Grade A Type III Equipment.
Pressure Tests for Submarine Usage:
The Navy Galaxy Series UPS System was tested
to atmospheric pressure within the range
of 750-1250 millibars, and maintained standard
operation to specification to the following
test pressures for 1 hour:
250 millibars above ambient (applied within
30 seconds and released within 30 seconds)
250 millibars below ambient (applied within
30 seconds and released within 30 seconds)
Ambient pressure of 1000 millibars
Some of the features shown above can
be incorporated on our standard UPS models – Nova Electric offers Rugged UPS
Systems for Naval Applications in all of
our standard rack-mount packages, from 1-6+
KVA. We can also incorporate these additional
features on our DC-AC Inverters and Frequency
Converters as well. If you have a unique
submarine or shipboard application that
calls for a rugged AC power source, please
don’t hesitate to contact us –
we have over 38 years of experience designing
and manufacturing America’s best
power conversion equipment for harsh
environment applications!
For
more information concerning Nova Galaxy Series
True On-Line UPS
email:
mike@novaelectric.com |
|