Applications This
FCU converts various input 3Phase voltages of 120/208 50/60Hz or 230/400V
50/60Hz to single Phase 220V, 50, 60 or 400 Hz(specify output frequency). It can be used in test systems
where the input frequency and voltage are not suitable, or in places where 3
Phase power is available in abundance, but single phase power is very limited.
The unit is particularly suitable for apparatus that requires a 400Hz
source, such as airborne or shipboard systems. |

12.50" (W) x 17" (D) x 9" (H) |
|
Electrical Specifications:
Input: 220/400V
3 Phase (Specify Delta or Wye)
Output: 230 V Single Phase.
Frequency: 50, 60, or 400 Hz (specify).
Voltage Regulation: +
2% NL to FL.
Frequency Regulation: +
0.5%
Harmonic Distortion:
5% THD, 3% SHD.
Power Factor:
0.7 lead to 0.7 lag.
Efficiency at full load: 90% typical.
Overload:
125% for 5 minutes.
MTBF:
Over 30,000 Hours per MIL-HDBU 217
MTBR:
30 Minutes.
|
Environmental Specifications:
Operating Temperature:
-20 șC to 50 șC
Storage Temperature Range: -40
șC to + 85 șC
Humidity:
to 95% non-condensing
Elevation:
15,000 Ft. (4.572m) operating; 40,000 ft (12.192m) non-operating.
Shock:
20g 11ms half sinewave.
Audible
Noise: Less than 55 dBA at
5 ft.
|
|
Standard
Indicators:
Input,
Output, Overload and Over temperature
Output
Voltage and Current Meters.
Protective
Features:
Current
Limit, Short Circuit Protection, Thermal Protection. |
Mechanical Specifications: