THE
EFFECTS OF EXTREME TEMPERATURES ON BATTERIES
NOVAS
RUGGED GALAXY-SERIES RACK-MOUNT UPS SYSTEMS HAVE
AN OPERATING TEMPERATURE RANGE OF 20 TO
+50 DEGREES CELSIUS, WHILE THE STORAGE TEMPERATURE
LIMIT IS 40 TO +60 DEGREES CELSIUS. HOWEVER,
USERS SHOULD BE ADVISED THAT HIGH TEMPERATURES
POSE A SIGNIFICANT PROBLEM FOR THE BATTERIES USED
IN (OR WITH) NOVA ELECTRIC (OR ANY OTHER BRAND)
UPS SYSTEM SYSTEMS. EVEN THOUGH THE STANDARD SEALED,
MAINTENANCE FREE BATTERIES USED WITH NOVA UPS
SYSTEMS ARE RATED FOR USE UP TO 50 DEGREES CELSIUS,
HIGH TEMPERATURES SERVE TO DECREASE THE OVERALL
BATTERY LIFE EXPECTANCY. SPECIFICALLY, AT 50 DEGREES
CELSIUS, THE BATTERIES WILL SELF-DISCHARGE AT
A RATE OF UP TO APPROXIMATELY 0.75% PER DAY. FURTHER,
LIFE EXPECTANCY OF THE BATTERIES USED AT 50-60
DEGREES CELSIUS IS REDUCED TO THE RANGE OF 9-18
MONTHS, AS OPPOSED TO A LIFE EXPECTANCY OF 3-5
YEARS FOR BATTERIES USED IN THE IDEAL AVERAGE
OPERATING TEMPERATURE OF 25 DEGREES CELSIUS. CONVERSELY,
LOW OPERATING TEMPERATURES OF -20 DEGREES CELSIUS
AND BELOW SIGNIFICANTLY REDUCE RUN-TIME FROM THE
RATED AMOUNT TO ALMOST ZERO! IF LOW TEMPERATURES
ARE PART OF YOUR APPLICATION, PLEASE BE SURE TO
COMPENSATE FOR THE REDUCED RUN TIME BY INCREASING
THE RATING OF YOUR BATTERY SYSTEM CONSULT
THE FACTORY FOR DETAILS. FOR MORE INFORMATION,
BATTERY CHARACTERISTIC CHARTS ARE AVAILABLE UPON
REQUEST FROM THE FACTORY SO THAT USERS CAN SEE
THE NEGATIVE EFFECTS OF PROLONGED EXPOSURE TO
EXTREME TEMPERATURES ON BATTERY LIFE IN MORE DETAIL.
PLEASE
NOTE THAT ON CERTAIN UPS SYSTEMS, WE ALSO OFFER
PREMIUM HAWKER ENERGY BATTERIES. THESE SPECIALIZED,
SUPER-RUGGED BATTERIES ARE LESS SENSITIVE TO TEMPERATURE
FLUCTUATIONS THAN THE STANDARD BATTERIES, AND
ARE ALSO MUCH MORE RESISTANT TO SEVER SHOCK AND
VIBRATION APPLICATIONS. THESE BATTERIES ALSO HAVE
IMPROVED WEIGHT / RUN TIME RATIOS FOR SHORT RUN
TIME APPLICATIONS. PLEASE CONSULT THE FACTORY
FOR FURTHER DETAILS.
|