3 PHASE MODELS
SPECS/STD FEATURES
AVAILABLE OPTIONS
  JUPITER SERIES
 
RUGGED, 240 VDC
DC-AC INVERTERS

210-280 VDC Operating Input / Pure Sine-Wave Output
10 KVA - 200 KVA


• Submarine and Shipboard Power Systems
• Aluminum Mills
• Steel Mills
• Cranes
• Heavy Industry
• Military Applications
• Single Phase Output Models Available


 
Partial Standard Model Selection

(Consult factory for custom applications)



3 PHASE MODELS

OUTLINE DWG.
(PDF)

3-PHASE
MODELS*
OUTPUT
VAC
OUTPUT
FREQ
(Hz)
CONTINUOUS
OUTPUT
POWER
APPROX.
WEIGHT
(LB)
SIZE
(H x W x D)
(INCHES)
J10K3/6-240(120/208)
120/208
60
10KVA
640
63x22x31.5
J10K3/5-240(220/380)
220/380
50
10KVA
660
63x22x31.5
J20K3/6-240(120/208)
120/208
60
20KVA
770
63x22x31.5
J20K3/5-240(220/380)
220/380
60
20KVA
790
63x22x31.5
J30K3/6-240(120/208)
120/208
60
30KVA
990
63x22x31.5
J30K3/5-240 (220/380)
220/380
50
30KVA
1010
63x22x31.5
J40K3/6-240(120/208)
120/208
60
40KVA
1210
63x22x31.5
J40K3/5-240(220/380)
220/380
50
40KVA
1230
63x22x31.5
 
J50K3/6-240(120/208)
120/208
60
50KVA
1540
63x44x31.5
 
J50K3/5-240(220/380)
220/380
50
50KVA
1580
63x44x31.5
 
J60K3/6-240(120/208)
120/208
60
60KVA
1760
63x43.5x31.5
 
J60K3/5-240(220/380)
220/380
50
60KVA
1800
63x43.5x31.5
 
J80K3/6-240(120/208)
120/208
60
80KVA
1980
63x43.5x31.5
 
J80K3/5-240(220/380)
220/380
50
80KVA
2040
63x43.5x31.5
 
J100K3/6-240(120/208)
120/208
60
100KVA
2420
63x43.5x31.5
 
J100K3/5-240(220/380)
220/380
50
100KVA
2490
63x43.5x31.5
 
J120K3/6-240(120/208)
120/208
60
120KVA
3300
63x87x31.5
 
J120K3/5-240(220/380)
220/380
50
120KVA
3410
63x87x31.5
 
J160K3/6-240(120/208)
120/208
60
160KVA
3960
63x87x31.5
 
J160K3/5-240(220/380)
220/380
50
160KVA
4100
63x87x31.5
 
J200K3/6-240(120/208)
120/208
60
200KVA
4840
63x87x31.5
 
J200K3/5-240(220/380)
220/380
50
200KVA
4900
63x87x31.5


BACK TO TOP



• Complete input to output ‘Galvanic’ isolation.
• High frequency almost silent operation
• Push button starting and stopping
• Diagnostic panel with LCD and LED display
• Soft start on inverter
• Overload & and short proof on and inverter
• True on-line Operation
• Optional Solid state transfer switch built in
• Optional Maintenance bypass switch built in
• All electronics are built in modular front access and front removable sub assemblies for easy service and maintenance
• FCC class A approved
• Remote isolated dry relay contacts
• Available options to meet military specs, including MIL-STD-461, MIL-STD-167, MIL-STD-810


MONITORING FEATURES


The Inverter includes an RS232 communication option called UPSCOM. This is an RS232 connection to a PC that can monitor in real time the three phase information related to the UPS output and any abnormal conditions that have occurred. Standard commercially available software is provided. The RS232 Feature is included at no additional charge.

Front Panel LCD display and LED indicators.

This will report all Inverter parameters. These includes input and output voltages, currents, frequency, DC voltage and current, as well as many other functions.

LCD Display.

Real time status, data or historical events are displayed and the LCD display. The Inverter parameters, real time clock, inverter, buzzer also can be set through this LCD, The LCD is back lighted by LEDs.

Status LEDs.

A series of LEDs representing all the important information of the Inverter provide information to the user. These LEDs are especially important when abnormal conditions occur. LED descriptions are as follows:

INVERTER ON - Inverter is running normally.

INVERTER SS - Inverter static switch is on while the reserve static switch is opened (off).

SHORT CIRCUIT – Inverter output is in short circuit state.

FUSE / OVERTEMP SD – Inverter has shutdown due to either fuse open or the temperature is too high.

INVERTER FAIL SHUTDOWN – Inverter has shutdown due to inverter AC output voltage too low.

BYPASS ON SHUTDOWN – Inverter shutdown due bypass breaker is closed when the inverter is running.

HIGH DC SHUTDOWN – Inverter shutdown due to DC bus too high when the inverter is running.

OVERLOAD SHUTDOWN – Inverter shutdown due to overload of the inverter for a period greater than the inverter can accept. The inverter will start after 7 seconds.

70% LOAD – load connected to the output is over 70% of the UPS rating.

110% LOAD – load connected to the output is over 110% oh the UPS rating.

125% LOAD - load connected to the output is over 125% of the UPS rating.

150% LOAD – load connected to the output is over 150% of the UPS rating.

RESERVE AC FAIL – reserve AC magnitude is out of range.

RESERVE FREQ FAIL – reserve frequency is out of range.

BATTERY LOW – DC bus (or battery) is lower than 160VDC, low battery shutdown will occur soon.

OTHER OPTIONS

DC INPUT BREAKER OPTION
The optional DC Inout breaker disconnect is offered to provide protection for the input.

SHOCK MOUNT OPTION
The cabinet can be shock mounted, using optional rubber on coil type isolators. This will be enable the unit to withstand shock levels as specified in MIL-STD-901

RUGGEDIZING OPTION
This option will add conformal coating and other additional internal structural members to allow the unit to meet many portions of MIL-STD-810.

TURN ON SERVICE OPTION
We offer a turn on service that will ensure the Inverter has been properly installed and the full warranty is in effect (failures caused by incorrect installation are not covered by the warranty.) If this option is selected, the customer will also automatically receive an additional 3 months added to the warranty at no additional charge.

SPARE PARTS KIT OPTION
We offer a spare parts package that includes one of each board, spare fuses, spare semiconductors, and spare fans. These spare part kits are priced lower when ordered with the initial order then if they are ordered later on.

 

BATTERY LOW SHUTDOWN – inverter shutdown due to DC bus (or battery) is lower than approximately 100VDC (lower than the acceptable DC voltage of the inverter).

HIGH DC – DC voltage over 150 VDC and the bus voltage will be limited to this voltage

EMERGENCY STOP – Inverter shutdown due to emergency stop switch pushed.

DATA LINE – Blink when data is transmitted to or received from the communication port.

Warning LEDs.

When abnormal condition occurs, these LEDs will light to warn the user of the cause of the fault condition. Therefore all these LEDs are off under normal condition. These LEDs are:

RESERVE FAIL – Reserve AC input is abnormal either due to AC magnitude out of range or frequency out of range.

FUSE/TEMP - Either inverter fuse is open or over temperature has occurred.

OVERLOAD – Output is overloaded by over 110%, 125% or 150%

HIGH DC – This LED will light as long as the DC voltage is over 140VDC.

BAT LOW – This LED will light when the DC voltage is lower than 100VDC.

BAT LOW STOP – This LED will light when the DC voltage is lower than 147.5VDC, inverter on is inhibited.

FAULT – The inverter is off due to abnormal conditions such as overload, short circuit, high DC, fuse over temperature, bypass breaker on emergency stop.

Since these LEDs are located behind the transparent window, the user can use them clearly without opening the door.

AUDIBLE ALARM – The audible alarm will beep under either one of the following conditions:

INVERTER IS OVERLOADED-
> 110% beep once every 3 seconds
> 125% beep once every second
> 150% beep twice every second

INVERTER IS SHORT CIRCUITED – Beeps continuously

FUSE OPEN
– Beeps continuously

HEAT SINK OVER TEMPERATURE
– Beeps continuously

HIGH DC SHUTDOWN
– Beeps continuously

BYPASS ON STOP
- Beeps continuously

EMERGENCY ON STOP
- Beeps continuously
The buzzer will also beep once every time the inverter is switched on or off to acknowledge to the user that his key entry is valid and accepted.

COMMUNICATIONS OPTIONS
We offer options for communications with this UPS series. Some popular options available at additional cost include the following:

UPSCAN: This is a hand held remote display and control module with LCD and LED display that can monitor via RS-485 UP to 99 UPS Units at a remote distance of up to 3,000 feet.

UPSCALL: This is a modem that will automatically dial out to a specified number when an abnormal situation occurs.

NETAGENT: This provides capability to monitor the UPS over the internet. It includes the appropriate additional SNMP card and microprocessor. The software required is provided by MEGATEC at additional cost.

BACK TO TOP

Specifications for the Nova Jupiter 3 Phase Inverter Series

PHASE
3-Phase Input/ 3-Phase Output
KVA
10
20
30
40
50
60
80
100
120
160
200
INVERTER  
Output Voltage (VAC)
Please Specify |120/208 |220/380 |230/400 |240/415 |277/480 |120 delta|220 3delta |240 3delta |380 3delta |480 3delta
Wave Form
Sinewave
Output Power Factor
0.7 lead to 0.7 lag
Frequency Lock Range
50 / 60 Hz + 0.1 Hz (crystal controlled)
Output Frequency (free running)
60Hz or 50Hz (please specify)
Phase Shift Under 100% Unbalanced Load
<0.5%
THD (Linear Load)
2% typical 3% max
Overload
<110%
Continuous
110-125%
15 minutes
125-150%
10 minutes
>150%
1 minute
Efficiency (100% Load)
90%
90%
90%
90.5%
90.5%
90.5%
90.5%
90.5%
90%
91%
91%
91%
STATIC SWITCH (optional)  
Voltage Range
Same as AC output. (Different voltages are available upon request)
Mains <-> Inverter
0 ms (True Online)
BTU/h @ Full Load (Approx, Max)
2.4K
4.8K
6.5K
8.9K
10.3K
12K
16K
19K
22K
30K
45K
Audible Noise
<65 dBA (at 1m)
<67dBA (at 1m)
Temperature
0-50ºC (32-122ºF) (Other ranges available)
Humidity
0%-90% (Non-condensing)
Altitude
Up to 1500 m Above Sea Level
EN50091-1, -2
Yes
Short Circuit Protection
Yes
Lightning / EMC Filter
MOV / Input & Output ( FCC CLASS A)
Galvanic Isolation
Input and Output True Galvanic Isolation
LED, LCD, Audible Alarm
Yes
Remote Control / Communication Interface
Monitoring 1~99 Units simultaneously / Dry Contact, RS-232, RS-485 (Optional)