int_nav.gif

 
 
 
 
 
 

Other Products


Charts/Graphs


MODEL SELECTION
SPECS/STD FEATURES
AVAILABLE OPTIONS
  24V rACK MOUNT
PURE SINE WAVE INVERTER
2000 W
 
RCGL 2K SERIES


The RCGL2K (pure sine wave) inverters are intended form commercial, industrial or military applications wherever standard utility-like power is needed at 50 or 60 Hz. These inverters are ideal for running electronic loads such as computers, monitors, printers, telecom systems, radios, fluorescent lamps from batteries, field generators, and solar electro-voltaic panels. They can also drive hand drills, motors and small compressors. This unit can be ruggedized against shock, vibration and humidity optionally for mobile applications.


Click to Enlarge
 

Model Selection

OUTLINE
DRAWING
PRODUCT
SPEC. PDF
MODEL
INPUT
RANGE
VDC
OUTPUT
VAC

OUTPUT
FREQ
(HZ)

CONTINUOUS
OUTPUT POWER
APPROX.
WEIGHT
(LB)
SIZE (HxWxL)
(INCHES)
RCGL2K-24-120
21-30 VDC
120
50 OR 60
2 KW
29
3.5 x 19 x 16.5

BACK TO TOP



OUTLINE
DRAWING
PRODUCT
SPEC. PDF
MODEL
INPUT
RANGE
VDC
OUTPUT
VAC
OUTPUT FREQ
(HZ)
CONTINUOUS
OUTPUT POWER
APPROX.
WEIGHT
(LB)
SIZE (HxWxL)
(INCHES)
RCGL2K-24-220
21-30 VDC
220
50 OR 60
2 KW
29
3.5 x 19 x 16.5

BACK TO TOP

 



• Microprocessor based design with absolutely stable frequency.
• Panel LED's for battery voltage & load level.
• Compact and light weight, yet rugged and vehicle rated.
• 93-95% efficient.
• Tightly regulated output voltage and frequency
• Switch selectable 50 or 60 Hz output.
• Capable of driving highly reactive loads such as electric tools and appliances.
• Capable of driving highly capacitive loads such as switching power supplies.
• Very low harmonic distortion, THD<3%.
• Suitable for vehicle mounting.
• Switch selectable ±10V output change.
• Load Controlled Cooling fan.

POPULAR OPTIONS

• MS Connector Mates
• Chassis Slides
• Additional Ruggedization against Shock / Vibration / Humidity to MIL-STD-810
• Weatherproofing Package (Sealed Breakers / Switches, additional dust filtration, and louvered air intake / exhaust for protection from splashing water – click here for outline drawing)
• Internal Electromechanical Transfer Switch

 

 



Input Voltage:
24 V
Output Voltag
e 110V model: 100/110/120 VAC
Output Voltage 220V model:
220/230/240 VAC
Output Frequency:
50 or 60 HZ User Selectable + 0.05% Accuracy
Continuous Power Rating:
2000W
Surge Rating: 4000W
Efficiency (full load):
120V model 92%
Efficiency (full load):
220V model 94%
No load Current:
<1.0W Sleep Mode
Output Waveform Sinewave:
<3% THD
Output Regulation:
+/-3%
Protection:
Overload, Short Circuit, Reverse Polarity (Fuse), O.T, Over/Under Input Voltage.
Operating Temperature: -20 to ° to +50°C
Storage Temperature: -40°C to + 71°C
MTBF: over 100,000 hours per field data
MTTR: 30 minutes
Shock: 20g / 11mS per MIL-STD-810
Vibration: per MIL-STD-810
Humidity: per MIL-STD-810 to 95% non condensing
EMI: per MIL-STD-461 CE102, CS101, CS114, CS115, CS116, RE102, and RS103
Size: 3.50 "H x 19"W x 16.5"L
Weight: 29 lb

SYSTEM COMPLIANCE

This unit is currently in use on military vehicle and shipboard applications worldwide, and has been formally qualified to:

MIL-STD-461E: CE102, CS101, CS114, CS115, CS116, RE102, and RS103

MIL-STD-810F: Environmental Engineering Considerations and Laboratory Tests

  • Low Pressure (Altitude) - Method 500.4, Procedure I (Storage/Air Transport) and Procedure II (Operation/Air Carriage)
  • High Temperature Method 501.4, Procedure I (Storage) and Procedure II (Operation)
  • Low Temperature Method 502.4, Procedure I (Storage) and Procedure II (Operation).
  • Temperature Shock Method 503.4, Procedure II (Cyclic)
  • Shock Method 516.5, Procedure VI (Bench Handling)
  • Vibration Method 514.5, Procedure I (General Vibration)
  • Humidity Method 507.4
  • Sand and Dust Method 510.4, Procedure I (Blowing Dust)

DC-AC INVERTER FAQ